A 32 by 24 infrared array can own one task inside a lift car: telling the controller that someone is present. It cannot own the close command until someone shows door-zone pixel coverage, measured false release and false hold rates, and a defined fail-safe path at that exact car. EN 81-20 draws the protected band between 25 mm and 1600 mm above the car door sill, and that band, not a development kit, is the acceptance target.
I have spent more time around retrofitted lift banks than around meeting rooms, and the pattern repeats. A cabin sensing program gets approved on an average accuracy figure and gets stopped on one edge case: a small body near the sill, a still passenger, a lens that nobody declared failed. The product literature is honest about what it is. The safety question begins where the literature stops.
The public record starts with a developer-facing write-up. It describes a Melexis MLX90642 People Detection Library aimed at elevators, offered in two modes, running on Cortex-M0+ and M4 parts, and bundled with the DVK90642 development kit. Privacy by design is claimed through local edge processing and thermal imaging, with no cloud streaming. The same material argues that the approach clears away the weaknesses of optical cameras, PIR (passive infrared) sensors and floor load cells, and it walks through the processing chain: dynamic background suppression first, then separation of thermal blobs, then spatial tracking.
Read plainly, that is a builder's case for counting bodies on a tiny processor. It is not an integrator's case for deciding when doors close. The mode split sharpens the difference: a Simple mode targets ultra-low-power Cortex-M0+ and M4 MCUs (microcontroller units), while a Default Full mode handles advanced multi-passenger counting on mainstream embedded processors. Occupancy reporting may well live in the low-power mode. A door hold mode would want higher pixel reliability, tighter latency margins and defined behavior under sensor faults.
Melexis keeps pushing the occupancy story. Its far infrared thermal array product page lists a 32 by 24 format and ties the device to people detection in ceiling mounted office scenarios, with applications across building automation, lighting control, surveillance, air conditioning and fire prevention. Packaged library, evaluation kit, real product family. That combination justifies occupancy trials, nothing more.
What the vendor added in 2025 makes the trial conversation more concrete. In an April 10, 2025 launch note, Melexis rates the MLX90642 at a NETD (noise equivalent temperature difference) of 65 mK at a 2 Hz refresh rate, configurable up to 16 Hz, with 768 pixels and two FOV (field of view) options, 45 by 35 degrees and 110 by 75 degrees, on an I2C-compatible interface. Those are usable baseline numbers for writing an acceptance test. None of them mention a door plane.
No, because the two jobs carry different failure costs. A Chinese journal article on lift platform overload detection reports experimental counting error below 5 percent using visual assistance. A trade post on elevator cabin cooling says buildings with revised climate control saw a 15 to 20 percent rise in user satisfaction. The first number describes counting under an experimental condition; the second describes comfort perception. Neither answers whether the system would withhold a close command when a passenger faces a wall, stands still, or presents a small warm area.
The code sets the real yardsticks. EN 81-20 requires the protective device, typically a light curtain, to cover the opening between at least 25 mm and 1600 mm above the car door sill, with detection resolution no coarser than 50 mm across the door path (Elevator World, review of the standard). On the timing side, door reopening devices must remain effective for not less than 20 seconds, as summarised by the U.S. Access Board guidance on ASME A17.1 and ADA elevator requirements. A thermal module that wants a seat at the close command has to be measured against those numbers, not against a people-count score.
| Dimension | Occupancy reporting | Door hold decision |
|---|---|---|
| Primary metric | Average count error, announcement rate | False release and false hold rate per 1,000 door cycles |
| Geometric target | Cabin volume, seating zones | 25 mm to 1600 mm above the sill, 50 mm detection resolution |
| Timing budget | Seconds of lag acceptable | Frames-to-presence and detection-to-controller latency bounded against a 20 second reopening window |
| Uncertain state | Can be suppressed to avoid chatter | Must be emitted, and must map to a defined controller action |
| Evidence owner | Vendor demo plus integrator spot check | Integrator, cabin geometry, controller architecture, equipment owner sign-off |
Resolution comes first. Research around thermal arrays explains why trials look promising while certification stays hard. An IBPSA paper describes typical formats as 8 by 8 or 32 by 32 thermal or infrared arrays. A Karlsruhe Institute of Technology paper notes lower spatial resolution, poorer image quality and more noise than visual sensors. Work published through MDPI, ResearchGate and the TADAR paper on arXiv leans on privacy, passive sensing, low cost and indoor activity or occupancy recognition. Those same strengths mark the edge of the evidence.
Few pixels plus a narrow or mismatched view means the detector can see a person and still miss the part that creates risk. A child sitting at the threshold, an arm caught near the sill, or a passenger close to a wall may occupy a small share of the thermal image. A PMC article gives a related example from wearable sensing: the Panasonic GridEYE AMG8833 has a 60 degree field of view focused on the upper portion. That is not an elevator specification, but it shows how an infrared array can be aimed above a hazard zone.
Temperature contrast creates a second failure mode. Thermal detection depends on differences, so warm seats, direct sunlight, a hot machine room, a cold beverage or heavy clothing can shift what a pixel reports. Chinese patent CN101883730A on passive elevator detection recognizes nonliving heat sources as false detection risks and proposes correction scans over the elevator's full travel, storage of hot source data, interpretation of periodic transients, distinction of unrepeatable transient sources by thermal profile temperature or shape, and sensitivity adjustment for human emission in the 8 to 14 micrometer band. The mitigation is useful, and it confirms the problem an integrator must verify.
Stillness is the third failure mode, and it collides with door timing. Chinese patent CN111199220A says foreground area or motion based top-down image methods perform poorly when objects are stationary, and that active infrared detection struggles when two or more passengers are close together or overlapping. Spatial tracking may help, but tracking still requires enough pixels and reliable separation between people.
One trade-off deserves an explicit line in the test plan, and I state it as analysis rather than as a vendor claim. The 65 mK NETD figure is quoted at 2 Hz. Running the same array at its maximum 16 Hz shortens the integration window per frame, which is exactly what a small, stationary, low-contrast target cannot afford. Any threshold tuned at one frame rate must be re-tuned and re-logged at the frame rate the installed product uses.
Certification wording outranks product naming. Depending on risk assessment and local rules, a module may be safety adjacent, safety relevant, or part of a safety function. The supplied public material assigns the library to no certification level, fault tolerance class or performance integrity category, and it carries no stated PL (Performance Level, ISO 13849-1) or SIL (Safety Integrity Level, IEC 61508) claim. Where a safety requirement names a maximum false release rate, that rate must be measured under cabin lighting, preheat and door cycle conditions. The library does not become unusable. The acceptance burden simply lands on the integrator, the cabin geometry and the controller architecture.
The system boundary is still open. Door hold logic interacts with the door operator, the controller, the beam curtain, the pressure edge and passenger behavior, and a library running on a microcontroller does not erase those interactions. Nowhere in the public material is there proof that the software can output a defined fail-safe state, report a blinded lens, flag sensor absence, or specify how a communication fault reaches the controller. Without that, the module is an occupancy input. The same discipline we apply when treating each cabin as a calibrated room applies here: geometry and thresholds first, model claims second.
It is a fair one. A light curtain can be the weaker witness for occupancy context. A beam curtain detects interruption; it does not decide whether a warm person is standing in the cabin. A suitcase can interrupt a beam, dirt can reduce range, and vibration can shift alignment. Thermal sensing works without visible light, avoids video and may provide a privacy friendly presence signal. The Melexis software runs on Cortex-M0+ and M4 parts, and the TADAR paper presents thermal array detection and ranging as passive, low cost and privacy preserving. Where a cabin already has a beam curtain, an array looks like a small, cheap addition.
That argument has force for scheduling, announcements, ventilation and load reporting. It weakens as a standalone safety case. Door hold must answer behavior at the edge of detection, and the false positive and false negative patterns documented in the public sources are precisely the patterns a safety gate must bound. A controller may need to hold a close command when the thermal signal is uncertain while the beam curtain still shows the door path clear. That is a different output contract from occupancy counting. A privacy friendly sensor can be cheap, passive and still unsuitable as the sole witness for a close command.
A better design puts the array beside the beam curtain. The curtain stays the object gate; the thermal signal supplies occupancy context, anomaly detection and a flag when the cabin heat map turns abnormal. If a project wants to shorten a door close cycle using thermal data, the array must show it does not create a false release at the door plane. That burden is larger than a demo in a development kit, and it is the same gap we keep tracing across pilot evidence tiers.
Field acceptance follows the shape that component and systems testing, on-site verification and commissioning already follow in building envelope work (UL Solutions, building envelope services): define the assembly, test it, then prove the installed unit matches it. For a cabin trial, that means eight steps.
The central judgment has explicit falsification conditions. If a supplier provides installation-level data for the exact cabin, the conclusion changes. The file should record how the array responds to a missing or blocked sensor, and how the controller behaves on a false hold, a false release and a communication fault. If those results meet the project's safety requirements and the owner accepts them, the thermal array can become part of a door hold decision.
Cabins will likely add passive sensors because they avoid visible video and fit small controllers. A thermal map can flag an occupied cabin that a load cell calls empty, a missing person that a beam curtain cannot see, or a heat signature that drifts away from expected door plane geometry. Those flags improve maintenance and operation. The boundary is whether an installed system can be trusted when the body is small, still, masked by geometry or wrongly absent.
The framework I hand to integrators has four gates, each with one exit test. Gate one, state contract: the detector can output empty, occupied and uncertain, and the controller has an action for each. Gate two, geometry proof: measured coverage of the 25 mm to 1600 mm band with the worst small target on record. Gate three, fault contract: blinded lens, absent sensor and communication loss each reach the controller as a defined safe state. Gate four, rate proof: false release and false hold counts over weeks of real door cycles, signed by the owner. Until those four gates close at the exact elevator, thermal libraries belong in occupancy and support roles, and door hold certification stays behind field evidence.
Not on the public evidence. The beam curtain is the object gate for the door path; the array is a presence and context signal. A replacement claim needs door-zone coverage, false release rates and a fail-safe output contract measured at the installed car.
Because a low-resolution array reports a small warm blob near the sill, and average counting accuracy hides that case. Risk lives at the edge of detection, not at the mean.
The rate the product runs at. The MLX90642 NETD figure of 65 mK is quoted at 2 Hz while the device is configurable up to 16 Hz, so thresholds and false negative behavior must be logged at the installed setting.
No. It settles the privacy argument. It says nothing about how a failed sensor, a blocked lens or a lost bus message reaches the controller, and that is where door hold evidence is usually missing.
The integrator, together with whoever owns the cabin geometry and the controller architecture. The vendor library supplies a building block, not an assigned safety integrity level.